Main Page
Further Thoughts
Low Pressure Compressors
BLOG
Favorite Links
Contact Me

Maxwell Demonology

Find out how you can heat and cool a home using only a single 2kw motor driven blower producing a pressure of 10 PSIG, with an outside temperature of 32 degrees. 
 
1, Preserving the heat you put into the home, as you recycle fresh air.
2, leaching heat from the outside freezing air!
3, simulteneously generatig bonus refrigerated air of -2 degrees F.
 
This is only one early scenario.
 
 
 

MRHeater.GIF

What differentiates a Ranke Maxwell Heater or Cooler from standared Multistage Vortex tube Technologies?
1, Low Pressures of 20 PSIG and lower, as opposed to the industry standard use of 20 PSIG and higher.
2, High volume air flow through large tubes.
3, The intentional exchange of differential temperature air with outside air to tap a free reservoir of heat.
IE: Exchange -2 degree output air with -32 degree outside air, to gain a free 34 degrees toward the target temperature, replace the heat preserved from the seventy degree inside air, raising the temperature to 81 degrees total.
 
 
 
This site is about finding the optimum low pressure heating configuration of Maxwell's Demon to achieve home heating costs of half or lower than half the cost of running a 100 percent efficient heater.            

  • Maxwells Demon can be used to transfer the heat in freezing cold outside air into a warm environment.

 

  • Using Maxwells demon for home heating requires two things, conventional technology and unconventional thinking.

 

  • The design considerations for the Maxwell / Ranque heater apply equally to the Maxwell / Ranque air conditioner, using the same components.

 

  • Computer logic can be used to reconfigure sequential Vortex Tubes.

 

  • The same system could be used to self optimize for heating and cooling, self optimizing to various climatic conditions.

 

The “Maxwell/Ranque Heater”

 Toward Home Heating through the use of Maxwell’s demon

 

 

If you could separate the air into volumes of hot and cold air, you could then throw away the cold air, and put the heat back in your home.

 

As long as you did this more efficiently than actually heating the air,

you would have more heat than you paid the utility company to produce!

 

Without the need for speculating about wild eyed plans to use that “Free” energy to generate even more “free” energy, and so on until you have the equivalent of Hoover Dam in my basement,  wouldn’t you still feel pretty good about the idea of maybe 1/2 off your heating bill!

 

It happens to be true that there is a device which can separate both hot and cold from air at the same time, using only compressed air. It is little more than a tube with a pipe T, a washer and a leaky plug, and it has no moving parts. And no, it is not an alien artifact; it is a common industrial tool.

Reference: http://en.wikipedia.org/wiki/Vortex_tube

 

If this new heater were made of parts which are entirely available “off the shelf”;

involving no new technology, only the proper arrangement of existing technology that would be even better.  This also happens to be true.

 

 

Now some readers will already be preparing the branch to hang me from, believing that I have provided enough rope to hang myself. That is, after I fall off the laws of thermodynamics provided conveniently by James Clerk Maxwell.

 

However we are going to enslave Maxwell's own Demon to help heat our hypothetical home. And you will have to argue with James Clerk Maxwell who’s equations lay  the foundation for special relativity and quantum mechanics.

 

Reference: http://en.wikipedia.org/wiki/Maxwell%27s_Demon

 

During Maxwell’s Lectures he speculated that if we had a tiny demon which could open and close a tiny valve in the wall of a box, we could separate the hotter and colder molecules of air by opening the valve only when a molecule of the right speed came along. This is because statistically the molecules are of varying temperatures. In this way we could change the temperature in the box.

 

We will use the vortex tube to take on the role of Maxwell’s Demon. The vortex tube is well known to the theoretical and industrial sides of engineering, with a number of well defined operational parameters.  The vortex tube has no moving parts, you blow air into the stem of a T shaped pipe of the appropriate internal design, and hot air comes out one end of the top of the T and cold out the other.

 

Reference: http://www.vortexair.biz/Cooling/SPOTCOOLPROD/Vortex_Technical/vortex_technical.html

PSI

Cold Fraction %

20

30

40

50

60

70

80

 20

61.5

59.5

55.5

50.5

43.5

36.0

27.5

14.5

24.5

36.0

49.5

64.0

82.5

107

40

88.0

85.0

80.0

73.0

62.5

51.5

38.0

20.5

35.0

51.5

71.0

91.5

117.0

147

60

104

100

93.0

84.0

73.0

59.5

44.5

23.5

40.0

58.5

80.0

104

132

168

80

115

110

102

92.0

80.0

65.5

49.0

25.0

43.0

63.0

86.0

113

143

181

100

123

118

110

99.0

86.0

70.5

53.0

26.0

45.0

66.5

91.0

119

151

192

120

129

124

116

104

90.5

74.0

55.0

26.0

46.0

69.0

94.0

123

156

195

140

135

129

121

109

94.0

76.0

56.5

25.5

46.0

70.5

96.0

124

156

193

Figures shaded in grey give temperature drop of cold air, degrees F

Figures on the second line give temperature rise of hot air, degrees F

 

Examination of this chart shows that for heat or cold extracted vs. power input required to achieve the higher compression values, the efficiency actually goes down with higher air pressures input, because it requires more energy to increase compression.

 

Each time the chart increases compression, less differential is gained between the value of the hot and cold outputs.

 

While the chart does not specify values for Power input to achieve compression, we know from experience that it becomes more and more difficult to press the bicycle pump down as the back pressure increases.

 

Referencing the chart for a cold fraction of 60 %:

The difference between the hot output between 120 PSI input and 140 PSI input is only + 1 degree hotter for the 20 additional PSI.

In other words:

The increase from 120 to 140 PSI has an input benefit of + 1 degree

The increase from 0 to 20 PSI has an input benefit of + 64 degrees

 

Clearly the lower pressure is more efficient.

 

 

It is a fact that there is progressively less benefit at higher pressures. And the decrease in efficiency is not linear.

 

This holds true from 120 PSI down to 20 PSI for a fact, and I expect it is true below 20 PSI.  The output is dependant upon the input temperature, and the difference between the input pressure and Cold Fraction output pressure.

 

I estimate based on a visual analysis of the trend in the bar chart (In the upper right corner) that the effect continues at increasingly lower differential values until the vortex ceases to form from lack of pressure.

 

 

Since vortex fans are able to create a vortex effect, I believe this leaves us with the option of going to fractional PSI increase values if we determine the temperature differential is sufficient for a desired number of vortex tube stages. 

 

However based on some projections and calculations, I believe the lowest practical pressure would be about 5 PSI.
 

There are many other wonderful facts posted on the site referenced above.

I highly recommend it. Making my first tube from brass fittings cost me around $ 40 

Since the tubes sell for around $ 100 dollars, the assurance of a successful reference tube is well worth the investment for the experimenter.

 

There are a number of other manufacturers available, but this one has the best documentation in my opinion.  I have no personal connection with them, and have not yet purchased a reference tube yet.

 

 

With lowering input pressure, the extremes of the hot and cold outputs are not as high and low, and the volume of air decreases; but not as rapidly as the power needed to compress the air. 

 

Efficiency in this case being how much electric power it costs to raise the output temperature of a volume of air N degrees.

 

For instance a fan has very low power consumption compared to high pressure compressor.  If we could heat the house using only a few fans, moving greater volumes at lower expense, this would consume much less electricity than a high pressure, high volume compressor.

 

We will ignore for the moment that with lower pressure we have lower air flow. This can be compensated for by using a wider vortex tube. The industrial vendor in the link supplies several sizes. So we can surmise that they can be scaled up for lower pressure, higher volume architectures. In fact references show the tubes being used in refinery processes and Natural Gas pipelines. These are of considerable dimension.   

 

For our current purposes we are interested in low pressure, and heating.

 

The Thermal Engineering community which knows the vortex tube extremely well  appears to be not particularly interested in either heating or low pressure operation with the vortex tube.  20 PSI seems to be as low as they care to explore. I find primarily references to cooling and high pressure characteristics explored on the web and indexed in the “literature”. The heat is rarely used for any purpose other than de-icing the cold side.

 

Also consider that industrial cooling often demands extremely low temperature outputs, requiring extremely high differentials, and extremely high input pressures.

But we are not about cooling here.

 

 

The value for minimum pressure which provides the maximum efficiency is   probably undefined by the Thermal Engineering community at large unless is not currently “public” knowledge.  I have not been able to find it, if it does exist.

 

Why?

 

When operating within the laws of thermodynamics, ignorance is no excuse!

 

Because of the high industrial pressures used to generate extreme temperatures, Vortex Tubes are considered horrendously inefficient!

 

Fortunately it will not be hard to determine if vortex tubes can be arranged to efficient low pressure home heating configurations.

 

            With an input temperature of 70 degrees as shown in the above table, Maxwell’s demon allows me to run the compressed air through a vortex tube at 20 PSI and 60 percent of the air goes out the Cold Fraction side. I gain 64 degrees from the input temperature on the remaining 40 percent of input going out the Hot Fraction side.

 

 For the purpose of demonstrating the theory, I can simply discard 60 percent of the air at 43.5 degrees colder than the 70 degree input as exhaust.

 

NOTE: I am arbitrarily throwing away a 43.5 degree temperature drop and still demonstrating a free additional temperature increase in the house. For home heating purposes the Cold Fraction is really a liability. This could be used toward refrigeration as a side benefit and that use might even make our task easier and more energy efficient on the whole.

OC 

Do you now believe that I have demonstrated that you do get Over-Unity or COP > 1 from a Vortex or Ranque Tube? Those are both ways of saying more energy out than put in. 

 

The truth is that there is no more energy in the room than when  we started.

When I dispose of the cold output, I  need to replace that air with an equivalent volume of more highly heated air, fortunately the demon stole some heat from the air which I am throwing away. I can use that to heat the fresh air, just as long as I find a place warmer than my coldest temperature air to dispose of it.  

 

I personally do not believe I am describing Over-Unity or COP > 1, because there was no expansion of the original air volume, “Normal Heating” causes expansion.

If this is either Over-Unity or COP > 1 then the distinction is only semantic anyway.

 

We transferred existing heat energy incidentally, and took advantage of this to get a statistically higher average temperature of the remaining air. No new energy was introduced into the universe during this experiment! No laws of Thermodynamics or Engineering scholars were violated.


Don't celebrate yet!

 

The real engineering problem comes after you gain the "Free Energy"?

 

To use this for home heating, you need to discharge the cold from the cold air output, outside the home. This is because you are simply separating the hotter and colder molecules of air.

 

“Simple separation” is a convenient over-simplification. Heat exchange within the vortex is vital to vortex tube operation. The heat exchange allows the tube to be more efficient at higher input air temperatures, and makes sequential configuration of multiple tubes possible.

 

Once again analysis of the chart reveals a pertinent fact. Approximately 60% of the air needs to be cold output for optimal efficiency in heating.

 

By discharging the air, you would be creating a vacuum in the house, sucking in exterior cold air to replace the separated cold fraction air.

 

WARNINING TO EXPERIMENTERS: I also fear incidentally separating the oxygen and discharging that outside, oxygen separation with vortex tubes has been done by NASA.  Removing the oxygen from your home can severely impact your respiratory health. You would not see, or smell the difference, but you might sense something is wrong as you pass into coma and death.

 

See NASA [PDF]

Progress in air separation with the vortex tube

 

To overcome the discharge problem I have two ideas:

 

 The first is to use a heat exchange system to a ground water source to "sink" some of the cold and recirculate the air back in at ground water temperature. In this way we gain the benefit of the difference between the colder output and the ground water temperature, The difference between the ground water temperature and the inside temperature becomes lost efficiency, as we now need to heat that to a comfortable inside temperature, however it is always necessary to introduce fresh air and heat that fresh air continually, so this helps to mitigate the inefficiency.

   

 This approach in its pure form is operationally limited by the differential with the outside temperature.  Once the outside medium becomes as cold as the Cold Fraction, there is no way to dump the cold.   (That is why I prefer ground water to air as a sink, air can get much colder than ground water naturally gets.)

                                      

The second idea is to use a multistage approach and cycle the hot or cold output through the input of another vortex tube. (See the referenced page above)

Cycling the hot output looks less promising on paper Cycling the cold output provides the ability to preprocess the majority of air at a low differential with a 20% CF and then reduce the 20% to as low as 4 % extremely cold output.

 

Efficiency increases with higher input temperatures and multistage vortex tubes have been successfully tested (But not to my knowledge, both together.).

 

In this way it  might be possible to gain a higher differential and exchange a smaller total fraction of extremely cold output for relative outside warmth.

 

 

It is also theoretically possible to freeze a large area of ground mass below the frost line. Though I do not have any idea on how that would be implemented in a practical way. But the possible seasonal cooling benefits might make it worth thought.

 

_______________________________________ Next Column ==>


 

 


vortextubechart.GIF

 

Here are some estimates about the practicality at 10 PSI.

The 60 % CF first stage tube has a 70 degree in, -22 degree CF drop with +32 degree HF rise. So the CF output is 48 degrees and the HF output is 102 degrees.

 

I conservatively halved the 20 PSI values used in the chart rather than trying to guess the continued rate of increase for the curve, so this should be conservative estimate if the curve holds true to 10 PSI.  The author of the chart warns that the values cannot be used for higher or lower pressures than shown in the chart. However the Author only justifies the statement for the above charted pressure values.

 

The 50 % CF second stage would have 48 degree first stage CF as input,  -50  degrees CF drop and + 50 degree HF rise.

 

So 30 % of the total volume is now -2 degrees F from the second stage

Since we halved the first stage cold CF used as input

30 % is now 102 degrees F from the second stage

And 40 % is now 102 degrees F from the first stage

 

Wow, is it getting hot in here?

 

Thank goodness we still have to dump the 30 % volume of -2 F air and replace that with 70 degree heated fresh air.

 

If the temperature outside is 32 degrees (Freezing) we should almost have enough cold to bring the inside air down to 80 degrees without having to open the window.

 

 

70% * 102 degrees

   .7 * 102
+ 30% * 32 degrees
   .3 * 32

_______________________________

= 81 degrees final inside temperature


A casual consideration of the conservation of energy will suggest that I am in horrible ERROR here. How in the world can I expect to be believed when I say that I am not creating energy when I end with a higher temperature than when I started?  

 

The vortex tube did not heat the room. The sum of the inputs equals the sum of the outputs. If you run the demon open in the middle of the room no average change in temperature for the whole room should be expected. This balance includes the heat from the compressor which is a perfect heater when it compresses the air. I believe it fair to say that it is also a perfect cooler when you release the pressure.  100% efficient in both directions.

 

I replaced 30 percent of the air at -2 degrees with freezing air. That amounts to  a positive 34 degrees borrowed from the freezing outside air. It may be Cool but it is also Hot!

 

So the vortex tube conserved some of the heat already in the house. It also allowed us to add heat by taking it from the freezing outside air. It is in the borrowing where we can potentially profit using a vortex tube.

 

We want to optimize the number of stages to produce the most efficient exchange volume and temperature.

 

 

Here is the big open question. How much energy does the compressor actually use to generate the low pressure, in high volume to heat the house?

 

Lowering the compression to a minimum is essential, so is using a compressor designed for high volume and low pressure

 

We can also benefit through higher permissible insulation values than are practicable today. The air in a home must be refreshed with a constant intake amounting to about 20 percent per cycle of circulating the entire contents.

 

If you circulate the contents twice an hour, then every 2.5 hours you need to reheat the entire volume, whether the insulation would have preserved the heat or not.

The “Maxwell / Ranque Heater” allows us to preserve the heat and cycle the air at a profit in heating efficiency!

 

_______________________________________


Any feedback would be appreciated, I will post all feedback unedited if it is signed and passes the fit for children’s eyes test.

 

Do not laugh at others expense; if you would not be immortalized being laughed at yourself!

 

 

 Joe Heeney, July 2, 2007

 

 

God bless America, lets take it back!

Please Feel Free to Mirror this site!

Please post copys of this page!

Please propigate this out into the public domain!

No one has my permission to restrict usage of these concepts in any way shape or form.

This is for the everyone and especially the children, and definately not for the benefit of any one individual or organization. No one should go cold. No one should be a slave to the utilities. Not in a world composed entirely of energy!

Any individual or organization my implement these concepts freely, for profit, personal benefit, benevolent purpose or amusement.  

http://mysite.verizon.net/vzewfm4h/maxwell-demonology

KWpsi.GIF

Please get in touch with any comments or reactions to my site.

  

Dedicated to enslaving Maxwell's Demon for the benefit of familys everywhere!

AENbanner25.gif

Alternate Energy Resource Network Webring
[ Join Now | Ring List | Random | << Prev | Next >> ]

 

Powered by WebRing.